Reading Configuration
Display Action Response
Press MENU
Press ENTER
1) Press MENU, if necessary, until "Reading Configuration" prompt appears.
2) Display advances to "dEc.Pt" (decimal Point).
Press ENTER
Press MAX
Press ENTER
DECIMAL POINT SUBMENU:
3) Display flashes previous selection for decimal location.
4) Scroll though the available selections and choose decimal location: FFFF. or FFF.F (also F.FFF and FF.FF ù if "Process" type was selected in the "Input Type" menu).
5) Display flashes "strd" message and advances to "Temperature Unit".
Note: Decimal point for Process input type is passive.
Press ENTER
Press MAX
Press ENTER
TEMPERATURE UNIT SUBMENU:
6) Display flashes previous Temperature Unit selection.
7) Scroll though the available selections to the temperature unit of your choice: ░F or ░C.
8) Display flashes "strd" message and advances to "Filter Constant".

Press ENTER
Press MAX
FILTER CONSTANT SUBMENU:
9) Display flashes previous selection for filter constant.
10) Scroll though the available selections: 0001, 0002, 0004, 0008, 0016, 0032, 0064, 0128. - Default is 0004

Press ENTER 11) Display flashes "stored" message only if change was made.
Note: For PID control select filter value 0001-0004. A filter value of 2 is approximately equal to 1 sec. RC low pass time constant.
IF Process was selected in the "Input Type" menu the display will advance to "Input SC & OFF", otherwise the display advances to the "Alarm 1"menu. 0001
Note: The Filter Constant submenu allows the user to specify the number of readings stored in the digital averaging filter.

Reading Configuration (If Process was selected)
Display Action Response
Press ENTER
Press MAX & MIN
Press ENTER
Press MAX & MIN
Press ENTER
INPUT SCALE & OFFSET SUBMENU:
12) Press enter at the "Inpt SC.0F" prompt. Display flashes 1st digit in submenu "In 1"
13) Use MAX and MIN buttons to enter "In 1" value. The "In 1" value = min. input value *the natural gain. Example: 4(mA) x 500 = 2000
14) Display advances to "RD 1" submenu.
15) Use MAX and MIN buttons to enter "RD 1" value. This value responds to In 1 in terms of some meaningful engineering units
16) Display advances to "In 2" submenu. The "In 2" value = max. input value *the natural gain. Example: 20(mA) x 500 = 10000 (9999)

Press MAX & MIN
Press ENTER
Press MAX & MIN
Press ENTER
17) Use MAX and MIN buttons to enter "In 2" value.
18) Display advances to " RD 2 " submenu.
19) Use MAX and MIN buttons to enter " RD 2 " value.
20) Display flashes "stored" message and advances to "AlAr 1" menu.
Note: This submenu allows the user to scale the meter when in process mode and the above display value is an example for 4-20mA input (4 to 20mA = 0000 to 0100%). RD 2 0100. 9999.

Figure 3.3 Flowchart for Reading Configuration
Figure 3.3 Flowchart for Reading Configuration

Alarm 1
Display Action Response
Press MENU
Press ENTER
1) Press MENU, if necessary, until "Alar 1" prompt appears.
2) Display advances to "Alar.1 enbl" or "dsbl" submenu.
Press MAX
Press ENTER
ALARM 1 ENABLE/DISABLE SUBMENU:
3) Display flashes previous selection. Press MAX until "Enbl" displays to use Alarm 1.
4) Display flashes "strd" message only if it was changed, otherwise press MENU to advances to "Control Type" submenu.
Press MAX
Press ENTER
ALARM TYPE SUBMENU:
5) Display flashes previous selection. Press MAX to "AbSo" or "dEu." Press ENTER
6) Display flashes "strd" message only if it was changed, otherwise press MENU to advances to "Alarm 1 Latch" submenu.
Note: Absolute mode allows Alarm 1 to function independently from Set Point 1. If the process being monitored does not change often, then "absolute" mode is recommended.
Deviation mode allows changes to setpoint 1 to be made automatically to Alarm 1. Deviation mode is typically the ideal mode if the process temperature changes often. In deviation mode, set Alarm 1 a certain number of degrees or counts away from Set Point 1 ù this relation remains fixed even if Set Point 1 is changed.

Press MAX
Press ENTER
ALARM LATCHED OR UNLATCHED SUBMENU:
7) Display flashes previous selection. Press MAX to Latched or Unlatched.
8) Display flashes "strd" message and advances to "Contact Closure" submenu
Press MAX
Press ENTER
CONTACT CLOSURE SUBMENU:
9) Display flashes previous selection. Press MAX to Normally Closed (n.c.) or Normally Open (n.o.).
10) Display flashes "strd" message only if it was changed, otherwise press MENU to advances to "A.P.on" Enable/Disable.
Press MAX
Press ENTER
ALARM 1 SETUP SUBMENU:
13) Display flashes previous selection. Press MAX to scroll through the available selections: Above, Below, HI/Low and Band (Band is active if "Deviation" was selected).
14) Display flashes "strd" message only if it was changed, otherwise press MENU to advances to "Alarm 1 Low Value" submenu.
Above: Alarm 1 condition triggered when the process variable is greater than the Alarm Hi Value. (Lo value ignored)
Below: Alarm 1 condition triggered when the process variable is less than the Alarm Low Value. (Hi value ignored)
Hi/Low: Alarm 1 condition triggered when the process variable is less than the Alarm Low Value or above the Hi Value
Band: Alarm 1 condition triggered when the process variable is above or below the "band" set around Set Point 1. Band equals Hi Value (Lo Value ignored). A "band" is set around the Hi Value by the controller only in the "deviation" mode.

Press MAX
Press ENTER
ALARMS ENABLE/DISABLE AT POWER ON:
11) Display flashes previous selection. Press MAX to enable or disable.
12) Display flashes "stored" message only if it was changed, otherwise press MENU to advances to the "Alarm Setup" submenu.
Note: If the alarm is enabled at Power On, the alarm will be active right after reset. If the alarm is disabled at Power On, the alarm will become enabled when the process value enters the non alarm area. The alarm is not active while the process value is approaching set point 1.
Press MAX & MIN
Press ENTER
ALARM 1 LOW VALUE SUBMENU:
15) Display flashes 1st digit of previous value. Use MAX and MIN to enter new value.
16) Display flashes "strd" message and advances to "Alarm 1 HI Value" submenu.
Press MAX & MIN
Press ENTER
ALARM 1 HI VALUE SUBMENU:
17) Display flashes 1st digit of previous value. Use MAX and MIN to enter new value.
18) Display flashes "strd" message only if it was changed, otherwise press MENU to advances to "Alarm 2" submenu.
Note: Latched mode: Relay remains "latched" until reset. To reset already latched alarm, select Alarm Latch and press Max twice (i.e. Unlatch and then back to Latch.)
Unlatched mode: Relay remains latched only as long as the alarm condition is true.
Normally Closed: "Fail Safe" mode, relay is energized under "normal" conditions and becomes de-energized during alarm or power failure.
Normally Open: If this feature is selected, then the relay is "energized" only when an alarm condition occurs.

Alarm 2
Display Action Response
Press MENU
Press ENTER
1) Press MENU, if necessary, until "Alar 2" display appears.
2) Display advances to "Alarm 2 Enable/Disable" submenu.
Press MENU
IF ALARM 2 IS NOT INSTALLED, THE CONTROLLER WILL SHOW "NOT INSTALLED"
Press MENU, if you receive the "not installed" message and advance to the "Loop Break" menu.
Press MAX
Press ENTER
Alarm 2 enable/disable Submenu:
3) Display flashes previous selection. Press MAX until "Enbl" displays to use Alarm 2.
4) Display flashes "strd" message only if it was changed, otherwise press MENU to advances to "Control Type" submenu.
The remaining Alarm 2 is identical to Alarm 1 i.e. previous two pages.

Modifying Alarm Settings will not reset the Controller

Figure 3.4 Flowchart for Alarm 1

Figure 3.4 Flowchart for Alarm 2
Figure 3.4 Flowchart for Alarm 1 and Alarm 2

Loop Break Alarm
Display Action Response
Press MENU
Press ENTER
1) Press MENU, if necessary, until the "Loop Break" prompt appears.
2) Display advances to "Loop Break Enable/Disable" submenu.
Press ENTER
Press MAX
Press ENTER
LOOP BREAK ENABLE/DISABLE SUBMENU:
3) Display flashes "enbl" or "dsbl".
4) Scroll through the available selections: Enable (enbl) or Disable (dSbl).
5) Display flashes "strd" message and advances to "Loop Value" menu.
Note: Loop Break is an additional safety feature intended to monitor the rate of change of the process value, while approaching the SPI. It is strictly intended as an additional warning system, therefore itÆs use is entirely optional. An active Loop Break will cause the Set Point digits to blink in a rotating pattern. If the process value reaches the set point the blinking will stop and Loop brA1 is completed successfully, otherwise Loop brA1 will flash and will activate Alr1.
Press ENTER
Press MAX & MIN
Press ENTER
LOOP BREAK ALARM VALUE SUBMENU:
6) Display flashes 1st digit of previous loop value.
7) Press MAX and MIN buttons to enter a new "loop value".
8) Display flashes "strd" message and advances to "CJ Temperature Adjust" menu.
Press ENTER
Press MAX & MIN
Press ENTER
TEMPERATURE ADJUST SUBMENU:
9) Display flashes 1st digit of previous temperature adjust value.
10) Press MAX and MIN buttons to enter a new "temperature adjust" value
11) Display flashes "strd" message and advances to "ID Option" submenu.
Note: Loop Break Alarm Value allows the user to determine the time interval in MM:SS (from zero to 99 minutes and 59 seconds) that the process value changes 10 counts or if the input type is either RTD or Thermocouple, the value would be ░4 Fahrenheit or 2░ Celsius. At the specified time interval, if the process value change is less than the stated rate flashing, " L.B.AL " will be displayed, the output "1" will be de-energized, and Alarm 1 energized. Loop break alarm will be disabled when the process value (PV) enters the control band.
Tip: Display Offset Adjust allows the user to fine tune a minor error of the transducer, however some applications may require a large offset adjust. (Displayed Process Value = Measured Process Value ▒ t.A.dJ). t.A.dJ is adjustable between -1999 to 9999.

Press MAX
Press ENTER
ID CODE OPTION SUBMENU
12) Display flashes current status of ID Option, enabled or disabled.
13) Press MAX button to select between Enable and Disable
14) Display flashes "strd" and advances to "Output 1."
NOTE: With ID Code Option disabled, the ID Number submenu is hidden. Refer to the appropriate Set Points section for setting differences.

Figure 3.5 Flowchart for Loop Break
Figure 3.5 Flowchart for Loop Break
Help Price List Specifications Print Manual Manuals Home
 Home Home  Table of Contents TOC  Back Back  Next Next